Supply Side Tap

A supply side tap is a connection that is made to the busbars or conductors on the line or utility side of the main service disconnect. The line side tap the simplest way of interconnection when installing a PV system that exceeds the 120% rule. (The 120% Rule - “What is it and why it is important?”)

When installing a supply side tap, you are physically connecting to a conductor or busbar. Below are some of the most common methods that are employed in performing a tap.

1169.jpg

Insulated terminal blocks. These terminal blocks are made to accommodate a variety of wire gauges. They require the service to be disconnected in order to install. The conductor being  tapped may be cut and landed individually on a three-hole version. These tend to be bulky and cumbersome in already cramped enclosures

Parallel tap connectors. These are similar to the terminal blocks in form and function. They promote more flexibility than insulated terminal blocks by allowing connections in cramped, overfilled enclosures. As with terminal blocks installations, the electrical service must be shutdown in order to install these.

Split bolt. These devices are relatively inexpensive and their ease of use make them a method of making a connection to a continuous service entrance conductor run. Like the terminal block, these devices are bulky, but offer a very sturdy connection.

Insulation-piercing tap splice connectors. This device pierces the conductor’s insulation to make electrical contact. These do not require you to have the electrical service shutdown.  This may be an added value where shutting down the service would interrupt essential services on-site. These devices are often very bulky, however, and may not fit in even mildly crowded electrical panels. The down side to this device is that it is very bulky.  So in enclosures that are full or extra wire makes space limited these could be ruled out.

Comments

Steve Thurman commented 4 years 1 month ago

How is it legal to tie a 100 amp wire to a 200 amp feeder without some form of protection I.e. 100 amp breaker to protect the smaller wire?

Thank you for your question.   A Supply-Side Tap is permitted by NEC 2011-2020 section 705.12(A) in earlier code years it was permitted by section 690.64(A). 

Lance Kent commented 3 years 2 months ago

Is a supply side tap still allowed under NEC2020?

Thank you for your post.

Yes, a lineside tap is still permitted by NEC 2020.

Terek Cope commented 2 years 11 months ago

What products do you offer in each category?

Take a look at our Balance of System (BOS)  and you can see a detail list of products. If you need additional help finding the products you need please complete a contact us form and we will put you in touch with a salesperson that can best help you. Thanks again.